По запросу
Артикул: GK24G-MF
Наличие: По запросу.
В корзину
Отправить запрос
АртикулGK24G-MF
Вспомогательные переключателиНет
Кабель1 м, 4 x 0.75 мм
Крутящий момент40 Нм
Питание24 В~/=
Площадь заслонки 8 м
ПрисоединениеУниверсальный захват
СерияGK_G
УправлениеПлавное 0…10 В= Рабочий диапазон 2…10 В= Настраивается

 

Electrical data
Nominal voltageAC 24 V, 50/60 Hz / DC 24 V
Nominal voltage rangeAC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V
Power consumption
In operation
At rest
For wire sizing

11 W @ nominal torque
3 W
21 VA (lmax 20 A @ 5 ms)
ConnectionCable 1 m, 4 x 0.75 mm2 (halogen-free)
Parallel operationYes (note the performance data)
Functional data
Torque
Inhibiting torque
40 Nm
40 Nm
Control
Control signal Y
Operating range

DC 0 … 10 V, input impedance 100 k
DC 0.5 ... 10 V
Position feedback (Measuring voltage U)DC 0.5 ... 10 V, max. 0.5 mA
Setting emergency position (POP)0% (POP rotary button end stop, left)
Bridging time (PF)2 s
Position accuracy±5%
Direction of rotation
Motor
Emergency setting position

As an option with /
Reversible with switch 0 ... 100%
Direction of rotation Y = 0 VAt switch position 1 or 0, respectively
Manual overrideGearing latch disengaged with push button
Angle of rotationMax. 95°, can be limited at both ends with adjustable mechanical end stops
Running time
Standard operation
Emergency setting position

150 s / 90°
35 s @ 0 ... 50°C
Automatic adjustment of running time, operating range and measuring signal U to match the mechanical angle of rotationManual triggering of the adaption by pressing the «Adaption» button
Override controlMAX (maximum position)= 100%
MIN (minimum position)= 0%
ZS (intermediate position, only AC)= 50%
Sound power level
Standard operation
Emergency setting position
53 dB (A) @ 90 s running time
52 dB (A) @ 150 s running time
61 dB (A)
Service life
Design life
Full cycles
Part cycles

15 years
100,000
1,000,000
Position indicationMechanical, pluggable
Terms and abbreviations
POP = Power off position / emergency setting positionPF = Power fail delay time / bridging time
Safety
Protection classIII Safety extra-low voltage UL Class 2 Supply
Degree of protectionIP66 NEMA 4, UL Enclosure Type 4
EMCCE according to 2004/108/EC
CertificationCertified to IEC/EN 60730-1 and IEC/EN 60730-2-14 cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02
Mode of operationType 1.AA
Rated impulse voltage0.8 kV
Control pollution degree4
Ambient temperature–30 ... +50°C
Non-operating temperature–40 ... +80°C
Ambient humidity100% r.h.
MaintenanceMaintenance-free
Dimensions / Weight
WDimensionsSee «Dimensions» on page 8
WeightApprox. 4.8 kg

 

Вернуться в Электроприводы Belimo IP66/NEMA4